TS816 Water Based Acrylic Top Seal is a waterborne, acrylic eggshell decorative top seal.
£79.75 – £83.19Price range: £79.75 through £83.19
TS816 Water-Based Acrylic Top Seal is a waterborne, acrylic eggshell decorative top seal. It is primarily for use with Nullifire intumescent basecoats on internal steelwork. Suitable for internal and semi exposed environments.
Provides a top seal to protect the intumescent coating while also providing an outstanding aesthetic finish to the steelwork.
Application Conditions
When applying Palatine Topseal, ensure that:
The product specification is appropriate for your intended requirements.
The basecoat is fully dried.
The surface finish of the basecoat is suitable for overcoating.
The correct dry film thickness (DFT) of basecoat has been applied before topsealing.
The equipment is of correct specification.
The site conditions and storage facilities are acceptable.
You are fully conversant with the Application Instructions prior to use.
Basecoat Condition: Ensure the Nullifire intumescent basecoat is fully dried and has reached the required Dry Film Thickness (DFT) specified for fire protection.
Surface Readiness: The basecoat surface must be clean, dry, and free from any contamination (dust, oil, or grease) that could interfere with adhesion.
Testing: Verify that the surface finish of the basecoat is suitable for overcoating. Intumescent basecoats can be moisture-sensitive; ensure the environment has remained dry.
Environmental Conditions:
* Apply only when air and steel temperatures are between 5°C and 25°C.
* Relative humidity should be below 80% (ideally below 65% for optimum drying).
* Ensure the steel temperature is at least 3°C above the dew point to prevent condensation.
Method: Can be applied by brush, roller, or spray. For higher-classified environments (e.g., C3), applying two thinner layers (e.g., 75 microns each) is technically preferred over a single thick layer to avoid defects like pinholes or misses.
Timing: Only apply the topseal once the intumescent basecoat is “thumb-nail” resistant (typically 24–48 hours after the basecoat is applied, depending on its thickness).
Thinning: This is a solvent-based coating. If thinning is required for spray application, refer to the technical data sheet for specific solvent/xylene-based thinner recommendations.
Fire Protection
Fire Protection
Fire & Flame Retardant Paint
Fire & Flame Retardant Paint
To provide the best experiences, we and our partners use technologies like cookies to store and/or access device information. Consenting to these technologies will allow us and our partners to process personal data such as browsing behavior or unique IDs on this site and show (non-) personalized ads. Not consenting or withdrawing consent, may adversely affect certain features and functions.
Click below to consent to the above or make granular choices. Your choices will be applied to this site only. You can change your settings at any time, including withdrawing your consent, by using the toggles on the Cookie Policy, or by clicking on the manage consent button at the bottom of the screen.